C7035A1023/U FLAME DETECTOR

Item #: 70294 
Manufacturer Item: C7035A1023/U
Manufacturer: HONEYWELL BUILDING/INTERNATION
72" Lead, 0 to 250 Deg F, Integral Nut for 1" Sighting Pipe Mount, Ultraviolet, Compact, Flame Detector
70294

Use with Honeywell Flame Safeguard Primary Safety Controls and Burners Requiring Ultraviolet Flame Detection

Mounts on a 1 Inch Sighting Pipe by Using an Integral Collar

Protects the Sensing Tube with a Shield

Wires in Parallel for Difficult Sighting Applications

Seals Against Pressures as High as 5 PSI When Correctly Installed

Field-Replaceable Ultraviolet Sensing Tube

Commercial Burner Controls

Type
Ultraviolet, Compact
Approval
UL, CSA, FM, RE
Operating Temperature
0 to 250 Deg F
Application
Coal/Gas/Oil Fired Burner
Enclosure
NEMA 3/4/4X
Mounting
Integral Nut for 1 Inch Sighting Pipe
Electrical Connection Type
(2) NEC Class 1 72 Inch Lead Wire